GE VersaMax IC200PWR001 User Manual page 71

Table of Contents

Advertisement

Specifications
Input Voltage
Input Power
Holdup Time
Inrush Current
Output Voltage
Protection
Output Current
Total
3.3 V DC Output
5 V DC Output
The Inrush current specification is given as a guide for sizing the
external power source. Peak inrush current may be higher for shorter
durations.
The total output current should not exceed 1.5 A. For example, if 3.3 V
at 0.25 A is required, 1.25 A is available on the 5 V output.
GFK-1504N
Chapter 3 Power Supplies
18 to 30 V DC, 24 V DC nominal
11W
10ms
20 A for 6 ms maximum at 24 V DC
25 A for 6 ms maximum at 30 V DC
5 V DC, 3.3 V DC
Short circuit, overload, reverse polarity
Standard power supply
(IC200PWR001G):
1.5 A maximum
0.25 A maximum
(1.5 A - I
maximum)
3.3 V
IC200PWR001
24 V DC Power Supply
Enhanced power supply
(IC200PWR002G):
1.5 A maximum
1.0 A maximum
(1. 5 A - I
maximum)
3.3 V
3
3-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents