GE VersaMax IC200PWR001 User Manual page 80

Table of Contents

Advertisement

3
Specifications
Input Voltage
Input Power
Frequency
Holdup Time
Output Voltage
Protection
Output Current
Total
3.3 V DC Output
5 V DC Output
The total output current should not exceed 1.5 A. For example, if 3.3 V
at 0.25 A is required, 1.25 A is available on the 5 V output.
Jumper Selection of 120 V AC or 240 V AC
This power supply can be used with either 120 V AC or 240 V AC nominal input
power. For 120 V AC nominal operation, a jumper should be installed as
marked on the power supply.
The power supply operates without a jumper installed; however, the hold-up
specification is not met. If a jumper is not installed for 120 V AC operation, the
power supply will not cause hazardous conditions.
DO NOT USE A JUMPER FOR 240 V AC OPERATION. If a jumper is used
on the input connector for 240 V AC nominal operation, the power supply
will be damaged and may cause hazardous conditions.
3-12
VersaMax Modules, Power Supplies and CarriersUser's Manual
120/240 V AC Power Supply
85 to 132 V AC with jumper installed, 120 V AC nominal
176 to 264 V AC w/o jumper installed, 240 V AC nominal
27VA
47 to 63Hz
20ms
5 V DC, 3.3 V DC
Short circuit, overload
1.5 A maximum
0.25 A maximum
(1.5 A - I
) maximum
3.3 V
JUMPER
FOR 120V
WARNING:
IC200PWR101
GFK-1504N