Error Messages

Current Share Error Codes

Current Share Error Codes

Table C.13Current Share Error Codes

Error
code
+1900
+1911
+1912
+1921
+1922
+1924
+1925
+1926
+1927
+1928
124
Error Message Description
Current Share General Error
Current share master already online
A unit on the CANbus network has already been assigned the current share
master unit. Only one is allowed per network.
Current share slave lost
One of the connected current share slaves have not responded in time.
Current share master lost
The assigned master has not responded in time.
Current share slave connection refused
Connection as a slave on the current share network has been refused due to
one of the following reasons:
4 slaves are already online,
the voltage rating does not match those of the master's,
the current rating does not match those of the master's.
Current share data out of range
The voltage or current readback or setpoint values passed are out of range.
Current share slave output off by unknown
One of the slave's output is off because of unknown reasons
Current share slave output off by command
One of the slave's output is off because of a command from a remote source
or the front panel.
Current share slave output off by AC fail
One of the slave's output is off because of an AC fail condition.
Current share slave output off by OTP (Over Temperature Protection)
One of the slave's output is off because of an OTP condition.