Additional Protections; Set Shutdown Recovery For Ac Off; Ac Off Protection; Over Temperature Protection - Xantrex GPIB-M-HPD Operating Manual

Multichannel functionality for programmable dc power supplies
Table of Contents

Advertisement

Additional
Other protection mechanisms designed to protect the power supply are:
Protections
Set
There are two options for AC Off (ACO) and Over-Temperature protection (OTP):
Shutdown
Recovery for
AC Off
AC Off
The user has the option of setting whether the AC Off protection mechanism is
Protection
latched or automatically resumes operation.
SENSe:VOLT:AC:PROT:LATCH {ON|1|OFF|0}
Where:
The default value is OFF.
To query if AC Off has tripped:
SENSE:VOLT:AC:PROT:TRIP?
Over
The user has the option of setting whether the OTP mechanism is latched or
automatically resumes operation.
Temperature
Protection
SENSe:TEMP:PROT:LATCH {ON|1|OFF|0}
The default value is ON.
To query if OTP has tripped:
SENSE:TEMP:PROT:TRIP?
Release 2.1
AC Off: Disables the output if the AC line drops below the acceptable range.
Sense Protection: Disables the output when the internal sense circuit is tripped
by either reversed polarity at the output of the supply or a high voltage present
at the output.
Output Fail: Disables the output if the bridge circuit fails. This is a hardware
protection circuit and has no associated software controls.
Auto-Recovery: With this method, the power supply returns to its normal
operating state once the alarm condition no longer exists. For example, if there
was an over-temperature alarm and the protection was set to auto-recovery, the
power supply would return to its normal operating state once the temperature
was reduced below the alarm level.
Latched: With this method, the power supply remains in Shutdown state until
the operator manually clears the protection and manually turns the output back
on.
ON or 1 means the supply will be latched in shut down if an AC Off condition
occurs, until the user re-enables the output, and
OFF or 0 means the supply will automatically resume operation when the AC
line input returns to normal.