Power On Output State; Reset; Table 3.2 Features Affected By Reset (*Rst) Command - Xantrex GPIB-M-HPD Operating Manual

Multichannel functionality for programmable dc power supplies
Table of Contents

Advertisement

Power On
(XFR/XHR only) You may also change the output state whether the output is enabled
or disabled at power on.
Output State
To change the power on at output state:
OUTP:PON:STAT [ON|OFF|1|0]
Whether the unit powers on with output enabled is a function of both the state at
power off and this setting.
Reset Resetting the unit puts certain features to a known state. These states are listed in
Table
To reset the unit:
*RST or SYST:RES

Table 3.2 Features Affected by Reset (*RST) Command

Feature
Voltage setpoint
Current setpoint
Low voltage setpoint limit
High voltage setpoint limit
Low current setpoint limit
High current setpoint limit
Over voltage protection
Under voltage protection
Over current protection
Under current protection
Fold shutdown protection
AC off shutdown recovery
OTP shutdown recovery
Triggered voltage setpoint
Triggered current setpoint
Autosequence mode
Calibration mode
Output
Release 2.1
3.2.
Reset State (*RST)
0.0V
0.0A
0.0V
101% of voltage rating
0.0A
101% of current rating
Disabled (0.0V)
Disabled (0.0V) and not shutdown when tripped
Disabled (0.0A) and not shutdown when tripped
Disabled (0.0A) and not shutdown when tripped
None and delay 0.5s
Auto recover
Latched
Disabled (Default)
Disabled (Default)
Exit
False
Disabled
Operation
Power Supply Operation