User Settings
If you have a frequent or constant need for a specific voltage and current output, you
can save these setpoints in the power supply's memory as a user setting. Once a
(Save and
setting is stored, it remains in the power supply's memory after the unit is powered
Recall)
off.
Ten user setting memory locations are available, and each saves the following
parameters:
Note All parameters are saved and used when the user setting is recalled. Therefore, you
should set parameters that you do not care about to the factory defaults.
To store (save) settings:
*SAV <user-setting>
or the SCPI equivalent for multichannel addressed units
SYST<channel>:SAVE <user-setting>
where <user-setting> is an integer from 1 to 10.
Example:
*SAV 1 will save all the present settings to user setting location 1.
To recall settings:
*RCL <user-setting>
To save default settings:
*SDS <user-setting>
Release 2.1
Voltage setpoint
Current setpoint
Over-voltage protection setpoint (OVP)
Under-voltage protection setpoint and shutdown configuration (UVP)
Over-current protection setpoint and shutdown configuration (OCP)
Under-current protection setpoint and shutdown configuration (UCP)
Foldback protection mode and delay settings
AC Off auto recovery configuration (ACO)
OTP auto-recovery configuration
Aux line configuration
Voltage and current soft limits
Triggered setpoints and trigger source
Operation
Power Supply Operation