Operation
1
Initial situation
4
Switch the three-position disconnector to
CLOSED position (insert the operating lever
and turn 90° clockwise).
214/293
26

Short instructions

The short instructions in this section give just an overview of the sequence of switching
operations.
➭ Read the description of the control elements, and observe the instructions for the
switching operations and the warnings specified in there (see page 186, "Operation" and
following).
26.1

Operating circuit-breaker panels (600 mm panel width)

Circuit-breaker panel: Connecting the feeder to the busbar
2
Push the interrogation lever downwards and
hold it.
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position. The actuating
opening closes).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
INFORMATION
3
Push the control gate to the left and hold it
(the interrogation lever locks in lower
position. The actuating opening for the
DISCONNECTING function opens).
6
To connect the feeder to the busbar, close
the circuit-breaker.