VOIS and CAPDIS indications

Hazardous voltage
Will cause death, injury or property damage.
Only valid for voltage indicators CAPDIS-S1+/S2+.
➭ Do not modify the factory setting of the C2 module in the voltage detecting system
CAPDIS-S1+/S2+ except with consultation with the regional Siemens representative.
➭ If the setting of the C2 module was modified by mistake, re-establish the factory setting as
follows:
- Pull out the C2 module at the rear side of CAPDIS-S1+/S2+.
ATTENTION: Open printed circuit board may be energized.
- Plug the C2 module into CAPDIS-S1+/S2+ so that the marked arrow on the housing
points to the marking on the C2 module.
Fig. 169: Marking of the factory setting on
the C2 module (example)
Fig. 170: CAPDIS-S2+: Cover
closed
Fig. 172: VOIS+: Cover opened
DANGER
Arrow
Marking on the C2 module
C2 module
Fig. 171: CAPDIS-S2+: Cover
opened
LC display
Test socket L1
Test socket L2
Earth socket
Test socket L3
Operation
LC display
"Test" button
Cover
Short instructions
Test socket L1
Earth socket
Test socket L2
Test socket L3
Duct for signaling
cables CAPDIS-M
205/293