Installation
88/293
Core drillings (incl. new plug systems)
For proper installation of the cable plugs, the following must be observed:
➭ Observe the specifications of the cable manufacturers.
➭ Drilling diameters depend on the cable cross-section.
Core drillings
• Circuit-breaker panel (panel width 450 mm, 630 A, 800 A)
Conductor distances
Make
1st cable
Plug type
3M
93-EE 705-6
Nexans Euromold
(K)400TB/G
(K)440TB/G
(K)430TB/G
(K)480TB/G
(K)484TB/G
Südkabel
SET 12/24
nkt cables
CB xx-630
CB 24-1250-2
CB 36-630(1250)
Tyco Electronics Raychem
RSTI-L56xx
RSTI-58xx
RSTI-x95x
GCA
CJBxx-630
ABB Kabeldon
CSE-A xx630-xx
CSE-A xx630-03
Cellpack
CTS 630A 24kV
Ample
AQT3-15/630
Solid-insulated bar
Moser-Glaser
Preissinger
Ritz
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
INFORMATION
2nd cable
Distance [mm]
Plug type
383
93-EE 718-6
383
- - -
383
- - -
383
(K)300PB/G
383
(K)800PB/G
383
(K)804PB/G
383
SEHDK 13.1/23.1
383
CB xx-630
383
CB 24-1250-2
383
CB 36-630(1250)
383
RSTI-CC-L56xx
383
RSTI-CC-58xx
383
- - -
383
CJBKxx-630
383
- - -
383
- - -
383
CTKS 630A 24kV
383
AHT3-15/630
- - -
372
- - -
- - -
1st cable
2nd cable
50...80 mm
Distance [mm]
275
- - -
- - -
278
273
273
273
283
283
273
283
283
- - -
268
- - -
- - -
268