Medium-voltage switchgear, fixed-mounted circuit-breaker switchgear up to 24 kv, extendable, single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

1
Initial situation
4
Switch the three-position switch-
disconnector to OPEN position (insert the
operating lever and turn 90° counter-
clockwise).
802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
Switch-disconnector, disconnector, ring-main or metering panels: Disconnecting the
feeder from the busbar
2
Push the interrogation lever downwards
and hold it.
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
3
Push the control gate to the left (the
interrogation lever locks in lower position.
The actuating opening for the
DISCONNECTING function opens).
Operation
231/293