Operating Switch-Disconnector, Disconnector, Ring-Main And Metering Panels With 600 Mm Panel Width - Siemens NXPLUS C Installation And Operating Instructions Manual

Medium-voltage switchgear, fixed-mounted circuit-breaker switchgear up to 24 kv, extendable, single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Operation
1
Initial situation
4
Switch the three-position switch-
disconnector to CLOSED position (insert the
operating lever and turn 90° clockwise).
230/293
26.4
Operating switch-disconnector, disconnector, ring-main and metering
panels with 600 mm panel width
Switch-disconnector, disconnector, ring-main or metering panels: Connecting the
feeder to the busbar
2
Push the interrogation lever
downwards.
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
3
Push the control gate to the left.