Floor Interlock And Operating Lever Adjusting Instructions - Siemens DPU Series Instructions, Installation, Operation, Maintenance

Vacuum circuit breakers (vehicle)
Table of Contents

Advertisement

Maintenance

Floor Interlock and Operating Lever Adjusting Instructions

The circuit breaker must be open and discharged prior to removing any covers.
Tools required:
• 1/2 inch wrench or socket (5DPR only)
• 7/16 inch wrench or socket
• 9/16 inch open end wrench
Adjustment tool 18-671-185-059, Steel Bar, 0.38 x 1.25 x 19.5 inches
m
m
• Midsize flat tip screwdriver
• Adjustment tool 18-671-185-059
Step 1
Move circuit breaker on to a smooth flat surface
Loosen hex-jam nut using a 9/16 inch wrench on
indicated clevis by turning it counterclockwise.
Turning the 3/8 inch rod counterclockwise moves
the roller down (decreasing clearance between floor
and roller).
Turning the 3/8 inch rod clockwise moves the roller
up (increasing clearance between floor and roller).
11