1
Initial situation
4
➭
Switch the three-position disconnector from
READY-TO-EARTH to OPEN position (turn
operating lever 90° counter-clockwise).The
circuit-breaker opens automatically
before the three-position disconnector
opens.
802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
Circuit-breaker panel: De-earthing the feeder with forced sequence circuit
2
➭
Remove the padlock (the locking device
goes down).
5
➭
Remove the operating lever (the control
gate returns to its initial position).
3
➭
Push the control gate to the right and hold
it.
Operation
219/293