Siemens NXPLUS C Installation And Operating Instructions Manual page 264

Medium-voltage switchgear, fixed-mounted circuit-breaker switchgear up to 24 kv, extendable, single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Operation
7
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
10
Switch the left-hand three-position
disconnector to READY-TO-EARTH position
(insert the operating lever and turn 90°
clockwise).
13
Push the right-hand control gate to the right
and hold it.
264/293
8
Push the interrogation lever downwards
again and hold it.
11
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
14
Switch the right-hand three-position
disconnector from READY-TO-EARTH to
OPEN position (insert the operating lever
and turn 90° counter-clockwise). The feeder
remains earthed through the left-hand
three-position disconnector.
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
9
Push the left-hand control gate to the right
and hold it (the interrogation lever locks in
lower position. The left-hand actuating
opening for the READY-TO-EARTH function
opens).
12
Close the circuit-breaker (the feeder is
earthed through the left-hand three-
position disconnector).
15
Remove the operating lever (the control
gate returns to its initial position).

Advertisement

Table of Contents
loading

Table of Contents