802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
Fig. 81:
Busbar support for 1600 A, 2000 A, 2500 A with
earthing connection points
Mounting the busbar support
➭ Mount the busbar support centrally on the busbars.
Fig. 82:
Mounting the busbar support
➭ Mount the earthing cable at the earthing connections of the busbar support and the
switchgear vessel or transformer mounting plate.
Busbar support
Earthing connection point at
the busbar support
Earthing connection point at
the switching-device vessel
Hexagon head bolt M10x75
Conical spring washer
Washer
Cable clamp (upper part)
Distance sleeve
Cable clamp (lower part)
Support
Earthing connection point
Installation
123/293