A Safety Instructions - Siemens Sentron LMD6 Series Information And Instruction Manual

Advertisement

Pressure Wire Connectors
A
DANGER
Hazardous Voltage.
i
t
I
088v--3/4-16
UNF-28
1.750
~
11.281
DO
Will
cause death or severe injury.
:I:
:I:
.437
I
Turn power off supplying switchboard
or panel before installing.
A
Safety Instructions
I
I
,1.
937
1
IOol~9
O~
TA3K500 Terminal Connector
General
Each connector kit contains a solderless connector and associ-
ated hardware for making one line or load connection.
Installation
NOTE: Trip unit must be installed in circuit breaker prior
to mounting load end connector.
A. Tighten mounting screws to securely attach connector.
See table for torque values.
B. Tighten set screws securely to prevent overheating of
conductor and connector. See table for torque values.
TA2N750 Terminal Connector
Connector
Circuit Breaker
Connector
Set Screw
Catalog Numbers
Ampere Rating
Wire Range
Torque
~~
,
500-600
(1-2) #1 AWG-500
375 in-Ibs.
,",~
kcmil (Cu/Al)
<~'\,"
TA2K500
~lJ
500-800
(1-3) #1 AWG-500
375 in-Ibs.
~
.. ;.:·i""
kcmil (Cu/AI)
TA3K500
~.
-'
.,.
500-800
(2) 600-750 kcmil
375 in-Ibs.
-
..
(Cu/AI)
TA2N750
8
1
,.875
D~E
For Use With
Type(s)
LMD6, LMXD6,
HLMD6, HLMXD6
LMD6, LMXD6,
HLMD6, HLMXD6
LMD6, LMXD6,
HLMD6, HLMXD6
t
f
4