Installation
138/293
➭ Place the left-hand side plate ① onto the switchgear termination ③ .
➭ Bolt the side plate together with the switchgear termination using 2 bolts M8x20.
➭ Bolt the side plate laterally together with the rear wall of the low-voltage compartment
using one self-tapping bolt M5 and one washer.
➭ Mount the right-hand side plate on the right end panel.
✔ The side plates of the horizontal pressure relief duct are installed.
If the installation of the top cover is not possible due to the height of the switchgear room, the
rear wall and top cover must be pre-assembled.
➭ Place the top cover on the rear wall.
➭ Bolt the top cover together with the rear wall using 3 bolts M8, and place it on the
switchgear.
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
INFORMATION
Side plate
Pre-assembled
evacuation
Switchgear termination