802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
Fig. 125: Mounted surge arrester (example)
16.5

Connecting surge limiters

You can only connect the surge limiter 3EH5 ... -5BA0 of Siemens (rated voltage
U
= 3.6 kV / 4.8 kV / 7.2 kV).
r
For connection at the cable connection, the following options are possible:
• Euromold
Use of the cable T-plug (coupling plug) 300PB-630A-U-BEGRENZ for connection of the surge
limiter.
• nkt cables
Use of the cable T-plug (coupling plug) CC 12-630, CC 17.5-630 or CC 24-630 in
combination with the assembly kit 26 500 33 for connection of the surge limiter.
• Tyco Electronics Raychem
Use of the cable T-plug (coupling plug) SMOE 63862 for connection of the surge limiter.
➭ Mount the surge limiters and the outside-cone plugs according to the manufacturer's
instructions.