Siemens NXPLUS C Installation And Operating Instructions Manual page 272

Medium-voltage switchgear, fixed-mounted circuit-breaker switchgear up to 24 kv, extendable, single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Service information
272/293
Detail view
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Component
Apply grease to the roller or latch.
Oil the stud connections.
Apply grease to the opening latch.
Apply grease to the curve of the opening
latch.
Oil the bearing for the operating shaft.
Apply grease to the deflection of the
auxiliary switch.
Apply grease to the end stop.
Oil the stud connection.
Apply grease to the bearing of the
contact pressure spring.
Apply grease to the dashpot.
Oil the stud connection.
Apply grease to the bearing of the
contact pressure spring.
Oil the stud connection.
Apply grease to the bearing of the
contact pressure spring.
Lubricants
Isoflex Topas L32
Shell Tellus Oil S2M32
Isoflex Topas L32
Isoflex Topas L32
Shell Tellus Oil S2M32
Isoflex Topas L32
Isoflex Topas L32
Shell Tellus Oil S2M32
Isoflex Topas L32
Isoflex Topas L32
Shell Tellus Oil S2M32
Isoflex Topas L32
Shell Tellus Oil S2M32
Isoflex Topas L32