Medium-voltage switchgear, fixed-mounted circuit-breaker switchgear up to 24 kv, extendable, single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

16
To de-earth the feeder, open the circuit-
breaker.
19
Switch the left-hand three-position
disconnector from READY-TO-EARTH to OPEN
position (insert the operating lever and turn
90° counter-clockwise).
802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
17
Push the interrogation lever downwards
again and hold it.
20
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
18
Push the left-hand control gate to the right
and hold it (the interrogation lever locks in
lower position. The left-hand actuating
opening for the READY-TO-EARTH function
opens).
Operation
265/293