Service information
270/293
Lubrication chart for 3AH25
Fig. 180: Lubrication chart overview for operating mechanism 3AH25
Charged operating springs
Can cause serious injury.
To lubricate some components, the operating springs must be charged.
➭ Do not reach into the operating mechanism compartment with your hands.
➭ Apply lubricant with a long brush.
➭ The operating springs must be uncharged after lubrication.
Detail view
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
WARNING
Component
Apply grease to the crank pins for
pushbutton operation.
Apply grease to the pushbutton
actuating plate.
Apply grease to the closing and opening
latch.
Apply grease to the curve contour.
Oil the bearing for the deflection lever.
Lubricants
Isoflex Topas L32
Isoflex Topas L32
Isoflex Topas L32
Isoflex Topas L32
Shell Tellus Oil S2M32