Operation
1
Initial situation
4
➭
Switch the three-position disconnector to
EARTHED position (insert the operating lever
and turn 180° clockwise).
236/293
Disconnector panel as of 2000 A: Earthing the feeder
2
➭
Push the interrogation lever downwards and
hold it.
5
➭
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
3
➭
Push the control gate to the right.