Object Description And Parameterization; Objects For Commissioning - Beckhoff EL6692 Documentation

Ethercat bridge terminal
Table of Contents

Advertisement

5.7

Object description and parameterization

EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.
Parameterization via the CoE list (CAN over EtherCAT)
The EtherCAT device is parameterized via the CoE-Online tab [} 96] (double-click on the respective
object) or via the Process Data tab [} 93](allocation of PDOs). Please note the following general CoE
notes [} 26] when using/manipulating the CoE parameters:
• Keep a startup list if components have to be replaced
• Differentiation between online/offline dictionary, existence of current XML description
• use "CoE reload" for resetting changes
Introduction
The CoE overview contains objects for different intended applications:
• Objects required for parameterization during commissioning:
◦ Restore object index 0x1011
◦ Configuration data index 0x80n0
• Objects intended for regular operation, e.g. through ADS access.
• Profile-specific objects:
◦ Configuration data (vendor-specific) index 0x80nF
◦ Input data index 0x60n0
◦ Information and diagnostic data index 0x80nE, 0xF000, 0xF008, 0xF010
• Standard objects
The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.
5.7.1

Objects for commissioning

Index 10F4 External synchronization status
Index (hex) Name
10F4:0
External synchroniza-
tion status
10F4:01
Sync Mode
10F4:0E
Control value update
toggle
10F4:0F
Time stamp update
toggle
10F4:10
External device not
connected
10F4:11
Internal time stamp
10F4:12
External time stamp
10F4:13
Control Value for DC
Master Clock
EL6692
Meaning
Information about the synchronization status
Synchronization mode
0 = no synchronization
1 = secondary side is Sync Master
2 = primary side is Sync Master
Bit toggles when a new control value is available
Bit toggles when new DC data were supplied
0 = other side is connected to its EtherCAT fieldbus
1 = other side is not connected to its EtherCAT fieldbus
Distributed clocks time on the current side (primary or
secondary)
Distributed clocks time on the other side (primary or sec-
ondary)
Offset for correction of the lower priority reference clock
Version: 3.2
Commissioning
Data type
Flags
Default
UINT8
RO
0x13 (19
BIT2
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
UINT64
RO
-
UINT64
RO
-
INT32
RO
0x00000000
(0
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec