secondary side must be checked for correct transmission of the configuration. The primary configuration may
need to be changed if the note shown in the fig. Warning messages for complex data types appears during
"Get Configuration".
Fig. 142: Warning messages for complex data types
Fig. 143: Warning message for complex data types
Application notes
Process data
The following must be observed in relation to the EL6692 process data:
• Data quantity
a maximum of 480 bytes can be transmitted in each direction.
• Number of variables
no more than 59 variables should be configured per side (primary/secondary) and data direction (input/
output). In total, 236 variables (4 * 59) can be cyclically transmitted.
• Alignment
The order of the variables of both data sides must be the same. In addition, 2-byte alignment must be
complied with. This is automatically created with Create/GetConfiguration.
EL6692
Version: 3.2
Commissioning
115