Object Description And Parameterization; Restore Object - Beckhoff EL34x3 Series Documentation

3-phase power measurement terminal
Table of Contents

Advertisement

Commissioning
• Actual sampling rate of the ADC (if different from the channel sampling rate)
• Time correction values for run times with different filter settings
• etc.
5.7

Object description and parameterization

EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description. We rec-
ommend downloading the latest XML file from the download area of the Beckhoff website and in-
stalling it according to installation instructions.
Parameterization via the CoE list (CAN over EtherCAT)
The EtherCAT device is parameterized via the CoE-Online tab [} 115] (double-click on the respec-
tive object) or via the Process Data tab [} 112](allocation of PDOs). Please note the following gen-
eral CoE notes [} 32] when using/manipulating the CoE parameters:
• Keep a startup list if components have to be replaced
• Differentiation between online/offline dictionary, existence of current XML description
• use "CoE reload" for resetting changes
Introduction
The CoE overview contains objects for different intended applications:
• Objects required for parameterization during commissioning:
◦ Restore object index 0x1011
◦ Configuration data index 0x80n0
• Objects intended for regular operation, e.g. through ADS access.
• Profile-specific objects:
◦ Configuration data (vendor-specific) index 0x80nF
◦ Input data index 0x60n0
◦ Information and diagnostic data index 0x80nE, 0xF000, 0xF008, 0xF010
• Standard objects
The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.
5.7.1

Restore object

Index 1011 Restore default parameters
Index
Name
(hex)
1011:0
Restore default parame-
ters [} 195]
1011:01
SubIndex 001
152
Meaning
Restore default parameters
If this object is set to "0x64616F6C" in the set value dia-
log, all backup objects are reset to their delivery state.
Version: 4.4
Data type
Flags Default
UINT8
RO
0x01 (1
dec
UINT32
RW
0x00000000 (0
)
)
dec
EL34x3

Advertisement

Table of Contents
loading

This manual is also suitable for:

El3413-0000El3413-0001El3413-0120El3433

Table of Contents