Technical data

Technical data
Connection technology
Width in the process image
Data transport time from one EtherCAT side to the
opposite side
Data transport method
Protocols supported
Support for distributed clocks synchronization
[} 110]
Supply voltage for electronics
Current consumption from the E-bus - supply,
primary side
Current consumption 24 V - supply, secondary side typ. 60 mA
Electrical isolation
Configuration
Weight
Permissible ambient temperature range during
operation
Permissible ambient temperature range during
storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting (housing with front unlocking [} 34] /
traction lever unlocking [} 33])
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
EL6692
EL6692
Primary side: E-bus
Secondary side: RJ45
max. 480 bytes in each direction
typical 1..4 ms
Asynchronous to the fieldbus
Cyclic process data AoE, EoE
yes (from TwinCAT 2.11)
via the E-bus
typ. 120 mA
500 V (E-bus/field voltage)
via TwinCAT System Manager
approx. 70 g
-25 °C ... +60 °C (extended temperature range)
-40°C ... +85°C
95 %, no condensation
approx. 26 mm x 100 mm x 52 mm (width aligned:
23 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
ATEX [} 39]
cULus [} 136]
Version: 3.2