3-16

Operating Temperatures and Fuel Selection

Use Table 9 to determine minimum return water temperature requirements:
TABLE 9 - MINIMUM RETURN WATER TEMPERATURES
Fuel
Natural Gas
Propane
#2 Fuel Oil
B100 Bio-Diesel
#2 Fuel Oil with guaranteed <15
ppm Sulfur (ultra-low sulfur)
Digester Gas/Alternative Fuels
VTG-IOM-2016-1214
Minimum Return Water Temperature
No minimum return water temperature
No minimum return water temperature
140°F (60°C)
100°F (38°C)
100°F (38°C)
Consult Factory