FULTON ICS Classic Series Instruction, Operation And Maintenance Manual

FULTON ICS Classic Series Instruction, Operation And Maintenance Manual

Gas fired steam boilers

Advertisement

Instruction, Operation,
Serial Number: _______________________________
and Maintenance
Model Number: _______________________________
Manual
Fulton Order Number: _______________________________
Fulton Gas Fired Steam
Sold To: _______________________________
Boilers
Job Name: _______________________________
HP to 60 HP
Date: _______________________________

Advertisement

Table of Contents
loading

Summary of Contents for FULTON ICS Classic Series

  • Page 1 Instruction, Operation, Serial Number: _______________________________ and Maintenance Model Number: _______________________________ Manual Fulton Order Number: _______________________________ Fulton Gas Fired Steam Sold To: _______________________________ Boilers Job Name: _______________________________ HP to 60 HP Date: _______________________________...
  • Page 3 Effective immediately, please use the limits below. Should you have any questions, please do not hesitate to contact Fulton at 315-298-5121. Water Chemistry Requirements for Fulton Steam Products (to 300 psig MAWP) Carbon Steel Stainless Steel...
  • Page 5 ASME Boiler and nance of your Fulton Gas Fired highest standards of manufacturing: Pressure Vessel Codes, for its Steam Boiler, and should be perma-...
  • Page 6  ...
  • Page 7 Contents Section Safety Warnings & Precautions For Boilers with Low Emissions Burner Only Description/Instructions Specifications & Dimensions 4-60 HP Locating the Boiler The Gas Supply Boiler, Condensate Tank, and Blow off Separator Piping Boiler Installation The Steam Supply The Steam Safety Valve The Steam Pressure Gauge Assembly The Blow Off Valve The Feed Water Piping...
  • Page 8   2-G 1/01...
  • Page 9: Safety Warnings/Precautions

    Safety Warnings/Precautions 3-G 1/01...
  • Page 10 4-G 1/01...
  • Page 11 NOTE up in the condensate tank.) CAUTION 4. Return pipes must not be insulat- After a new Fulton Boiler has been in ed. This can cause overheating the operation for several months, pieces return system, causing a vapor lock Do not tamper with the safety fea- of burned metal will be found in the tures of the low water safety cut off.
  • Page 12 6-G 1/01...
  • Page 13 Description/Instructions 7-G 1/01...
  • Page 14   8-G 1/01...
  • Page 15 Fulton Gas & Oil Fired Product Data Submittal Fulton Models: ICS/FB-A and ICX/FB-F Vertical Tubeless Steam Boilers (Low Emissions Burner) Dimensions Standard Models ICS/FB-A Models ICX/FB-F Unit Size: A. Boiler Height 67.5 63.5 72.5 74.5 1715 1613 1753 1842 1892 2083 B.
  • Page 16: Specifications

    +++Consumption based on Natural Gas 1000 BTU/ft. . *All ratings from 0 PSIG and at 212 degrees F. *** Control circuit electrical requirement will vary with the system voltage, please consult factory. --Consult factory. The Fulton Companies 972 Centerville Road Pulaski, NY 13142 Call 315-298-5121 Fax 315-298-6390 www.fulton.com...
  • Page 17: Operation

    Operation 11-G 1/01...
  • Page 18 12-G 1/01...
  • Page 19 UV Scanner. established flame. Should any fault occur, either during the ignition sequence or during normal running, Air adjustment for Fulton LE Gas the programmer will immediately go Fired Steam Boilers. to “lock-out” and the burner will shut down.
  • Page 20 14-G 1/01...
  • Page 21: Maintenance

    Maintenance 15-G 1/01...
  • Page 22 16-G 1/01...
  • Page 23 Refer to Fulton test fire report for acceptable ranges. 17-G 1/01...
  • Page 24: Troubleshooting

    The following lists cover the most “REMEDY”. information necessary to locate and common troubles that may occur on isolate possible troubles which the Fulton gas fired boilers. Refer occur during normal operation. It to left hand column of the chart to Troubleshooting Gas-Fired Boilers Problem...
  • Page 25 LE Maintenance Problem Cause Remedy Flame Failure 5. Scanner Check for dirt on flame scanner and clean. Check for proper location of detector. 6. Flame Safeguard Control Check voltage at terminal leading to main gas valve. If no power, replace the control. 7.
  • Page 26 LE Maintenance Problem Cause Remedy Poor Combustion 1. Refractories Check refractories to see if they are plugged with soot or broken in pieces. Clean or replace as necessary. 2. Air Adjustment Check main air adjustment to see if it is loosened up. Adjust as necessary and tighten plate in position.
  • Page 27 LE Maintenance Problem Cause Remedy Boiler is Surging 1. Steam traps blowing Check traps to see if they are clean or replace as necessary. through 2. Perc (cleaning solvent Clean boiler with washing soda per instruction manual. in boiler) 3. Scale build-up or lime Call water treatment professional and consult factory.
  • Page 28 LE Maintenance Problem Cause Remedy Water pump will not 1. Scale on probes Check and clean or replace as necessary. come on at times 2. Bad Pump Contactor Check to see if contactor is being powered. Check to see if contactor coil is pulling in. Replace if necessary.
  • Page 29 Parts 23-G 1/01...
  • Page 30 24-G 1/01...
  • Page 31: Spare Parts

    2. Boiler Type prices, specifications, and b. When ordering replacement or 3. Electrical Specifications equipment without notice. spare parts, make sure that the full Replacement Parts Listing (available from authorized Fulton Representative) Approx. Approx. Part No. Description Net Weight Net Weight (lbs.)
  • Page 32 26-G 1/01...
  • Page 33 Boiler Description/Instructions Gas Fired Boiler 27-G 1/01...
  • Page 34 Description/Instructions Transformer Scroll Burner Motor Gas Train Assembly QQQQQQQQQQQQQQQQQQQQQ Burner QQQQQQQQQQQQQQQQQQQQ Gaskets QQQQQQQQQQQQQQQQQQQQQ Plate QQQQQQQQQQQQQQQQQQQQQ Assembly QQQQQQQQQQQQQQQQQQQQQ Secondary QQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQQ O.P.C. Air Damper QQQQQQQQQQQQQQQQQQQQQ Steam Gauge QQQQQQQQQQQQQQQQQQQQ Top Plate QQQQQQQQQQQQQQQQQQQQQ Assembly Assembly QQQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQQ Flue Plate QQQQQQQQQQQQQQQQQQQQ Cover H.P.C. QQQQQQQQQQQQQQQQQQQQQ Flue Rope QQQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQ...
  • Page 35 Fulton Gas & Oil Fired Product Data Submittal Fulton Models: ICS/FB-A and ICX/FB-F Vertical Tubeless Steam Boilers (Standard Burner) Dimensions Standard Models ICS/FB-A Models ICX/FB-F Unit Size: A. Boiler Height 47.5 57.5 67.5 63.5 69.5 72.5 82.5 87.5 93.5 1207...
  • Page 36 ; Propane 2500 BTU/ft . *All ratings from 0 PSIG and at 212 degrees F. *** Control circuit electrical requirement will vary with the system voltage, please consult factory. --Consult factory. The Fulton Companies 972 Centerville Road Pulaski, NY 13142 ffsstd-pds-2011-1222...
  • Page 37 Description/Instructions 30-G 1/01...
  • Page 38 Description/Instructions SEE PRODUCT DATA SUBMITTAL ON PREVIOUS PAGES The Gas Supply the action of liquefied petroleum Locating the Boiler gases. Do not use teflon tape on a) Gas Piping should be installed in gas line threads. a) The boiler should be located in dry accordance with National Fuel Gas surroundings on a level base, making h) The main and the pilot gas pres-...
  • Page 39 Description/Instructions Basic Boiler, NOTE 3) Vent pipe should not be down- sized (this may cause pressure Where a condensate return tank is Condensate Tank, build up in the condensate tank). to be fitted, this should: and Blow off 4) Return pipes must not be insu- 1) Be vented to a safe lated.
  • Page 40: Gas Fired Steam Boiler

    If in doubt consult rear of the boiler, the gauge glass and/or local codes. The water col- a Fulton Representative for blow off valve, and the water col- umn blow off valve and the gauge advice.
  • Page 41 Description/Instructions Boiler Installation Steam The Steam Supply — Pipe the Pressure steam supply line from the top right Gauge side of the boiler. The Steam Safety Valve 1) Before installing, be sure that all pipes and connections have been (Open) Ball blown clean.
  • Page 42 Description/Instructions The Blow-Off Valve — There are two 4) Do not use the pump as a piping The Water Column blow off valves on the boiler: The support. It is critical that the pipe be main valve at the rear of the boiler independently supported near the Install the piping from the water and the water gauge glass blow off...
  • Page 43 Description/Instructions Water Gauge & Gauge Glass 9) Carefully slide upper glass pack- WARNING Installation instructions ing up as far as possible. Improper installation or mainte- NOTE 10) Hand tighten both glass packing nance of gauge glass and connec- nuts, then tighten 1/2 turn more by tions can cause immediate or Only properly trained personnel delayed breakage resulting in bod-...
  • Page 44 Various and are usually covered with tuber- polymers assist in holding solids in e) The Fulton Warranty does not cles of iron oxide. Once pitting starts, suspension. cover damage or failure that can be it may be extremely hard to arrest.
  • Page 45 Description/Instructions pH: pH is a measure of the degree Often oil in boiler water will origi- of acid or base of solution. Normal nate in the condensate. This conta- pH ranges of 6.5-9.0 will have little minated condensate should be influence on the corrosion rate of directed to the sewer until the cooling waters.
  • Page 46 Description/Instructions Electrical Requirements b) Proper ventilation of the boiler room is essential for good a) Connect wiring as shown in combustion. Install two fresh air Be sure total BHP = proper make the wiring diagram which is furnished openings, one at a low level (24”— up air opening size.
  • Page 47 Description/Instructions Conventional Venting c) The stack and chimney material Boiler Flue Size shall comply with all local codes. Inches Millimeters a) The stack should rise continuously to the connection with the chimney, d) Adequate provision must be and should contain no more than two made for the support of the weight of bends at 45 angles or less.
  • Page 48 Description/Instructions Exhaust Side Wall Venting (UL and Combustion Air Intake (UL and or perchloroethylene, when drawn MEA Approved- MEA File Number MEA Approved- MEA File Number into combustion air are broken down 68-79-E Vol. 2 ) 68-74-E Vol. 3 ) into elemental chlorine gas which exits up the flue pipe.
  • Page 49 Description/Instructions Installation Check Points 3) Mix washing soda with water in a 7) Generate 15 PSI (1.054 kg/cm one-gallon container and pour it into of steam and shut off the boiler. 1) Make sure all piping connections the boiler through the steam safety Allow this hot solution to remain in are complete and tight.
  • Page 50   42b-G 1/01...
  • Page 51: Operation

    Operation 43 -G 1/01...
  • Page 52   43b-G 1/01...
  • Page 53 Operation Starting the Gas Fired Boiler 3) Open main steam stop valve at NOTE the top of the boiler. Stop! Make sure you have read a) The fused disconnect switch and followed all previous safety that controls the feed water pump information.
  • Page 54 Fulton 4 - 30 h.p. natural gas fired boilers can be equipped with flame rods or UV scanners. f) All Fulton propane or butane boil-...
  • Page 55 Gas Burner Set Up For Boilers Equipped with Modulation a) Modulation is available as an option on Fulton gas fired steam boil- ers for 30 -100 HP units only. b) Boilers equipped with modulation will have the linkage rod disconnected between the modulation motor and the gas butterfly valve for shipment.
  • Page 56 Equipped with High-Low-Off a) A gas fired burner equipped for high-low-off firing is available as an option on Fulton gas fired steam boilers for 30 -100 HP units only. b) Boilers that have a high-low-off firing rate will have a linkage between the high-low gas valve and the primary air gate.
  • Page 57 Primary Air Adjustment for Fulton Gas Fired Steam Boilers a) The primary air adjustment or main air control is located at the fan hous- ing face.
  • Page 58 ASME CSD-1 Code full open, the ball will not seat. For controls also feature an independent added safety all Fulton boilers are second low water cut off relay. Press the low water reset button and the boiler will start.
  • Page 59: Maintenance

    Maintenance 5 -G 1/01...
  • Page 60   51-G 1/01...
  • Page 61 Maintenance Transformer Scroll Burner Motor Gas Train Assembly QQQQQQQQQQQQQQQQQQQQQ Burner QQQQQQQQQQQQQQQQQQQQ Gaskets QQQQQQQQQQQQQQQQQQQQQ Plate QQQQQQQQQQQQQQQQQQQQQ Assembly QQQQQQQQQQQQQQQQQQQQQ Secondary QQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQQ O.P.C. Air Damper QQQQQQQQQQQQQQQQQQQQQ Steam Gauge QQQQQQQQQQQQQQQQQQQQ Top Plate QQQQQQQQQQQQQQQQQQQQQ Assembly Assembly QQQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQQ Flue Plate QQQQQQQQQQQQQQQQQQQQ Cover H.P.C. QQQQQQQQQQQQQQQQQQQQQ Flue Rope QQQQQQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQ...
  • Page 62 Maintenance NOTE To ensure the continued safety and efficiency of the boiler, the sched- ule of maintenance outlined in this section should be adhered to. WARNING Prior to the commencement of any work requiring the removal of cover plates and the opening of the con- trol panel box, the electrical supply to the boiler must be disconnected.
  • Page 63 20-60 HP. b) A single flame rod is used on 4-15 HP Fulton Boilers, and two flame rods d) For the RM7800 Series use a key- on 20 and 30 HP. If the boiler has two...
  • Page 64 If the refractory will not tip, it may have to be Fulton factory. k) normal operation can be resumed immediately. removed and again rounded and beveled.
  • Page 65 If any leakage is evident, according to the manufacturer's replace the gaskets. instructions. NOTE Fulton recommends that the feed- water treatment should be added between the pump and the boiler. e) When first starting the boiler each day, make sure ignition and burner are working properly.
  • Page 66: Recommended Semi-Annual Maintenance Schedule

    Maintenance g) Remove brass pipe plug at the Withdraw the burner assembly and d) Check water pump for correct cross connection below water column clean the flame rod and ignition elec- operation. and clean nipple into boiler. Boiler trode. must be cold and water level below e) Shut off the boiler completely 2) Check that the settings of the pipe.
  • Page 67: Recommended Annual Maintenance Schedule

    Refill the boiler with fresh water. Removing hand hole assembly with a NOTE Tee Handle Wrench After a new Fulton Boiler has been 2) Remove the old gasket and thor- in operation for several months, oughly clean the surface on the boiler pieces of burned metal will be and the plate.
  • Page 68 The following lists cover the most “REMEDY”. information necessary to locate and common troubles that may occur on isolate possible troubles which the Fulton gas fired boilers. Refer to occur during normal operation. It left hand column of the chart to Troubleshooting Gas-Fired Boilers Problem...
  • Page 69 Maintenance Problem Cause Remedy Flame Failure 5. Flame Rod Adjustment Check flame rod for carbon buildup and clean if or UV Scanner necessary. Check flame rod adjustment via a display module. Flame signal should be 5 VDC. Check for cracks in porcelain. If found, replace. Check for dirt on flame scanner and clean.
  • Page 70 Maintenance Problem Cause Remedy Poor Combustion 1. Refractories Check refractories to see if they are plugged with soot or broken in pieces. Clean or replace as necessary. 2. S.S. Ring Check to be sure ring is present and fits tight against the furnace wall (50-100 HP).
  • Page 71 Maintenance Problem Cause Remedy Boiler will not 4. Scale Built up in boiler Refer to Section 2 “Pressure Vessel Cleaning”. maintain pressure 5. Refractories Check refractories to see if they are cracked or broken in pieces. Replace as necessary. 6. Steam traps Check traps to see if they are clean or replace as blowing through.
  • Page 72 Maintenance Problem Cause Remedy Pump runs but does 1. Vapor locking of pump. Allow system to cool down, check steam traps not put water into boiler and check to be sure return lines are not insulated. Check return tank temp. If it is above 180 deg. F, (82 deg. C) vapor locking of pump will occur.
  • Page 73 Parts 6 -G 1/01...
  • Page 74 ICS (FB-A) Classic & ICX (FB-F) Edge manual update: For all new ICS (FB-A) Classic boilers manufactured 2018 and after, the following updates have occurred: The ICX (FB-F) Edge model boiler has been discontinued. The ICS (FB-A) Classic is now configured as follows: •...
  • Page 75 Parts Spare Parts a) It is important that the correct replacement part is fitted to your Fulton Gas Fired Steam Boiler. b) When ordering replacement or spare parts, make sure that the full information given in the Parts List is...
  • Page 76 Parts Replacement Parts Listing (available from authorized Fulton Representative) Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 5-60-100 Instruction Manual, Fuel-Fired 0.91 5-60-165 Certification Papers 5-60-164 Boiler Documentation for Export Boilers Boiler Shell Parts 5-12-004 Furnace Refractory 8" OD x 2" ID (9.5 HP Top) 4.55...
  • Page 77 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 5-21-302 Steel Jacket 10 HP - No Holes Cut 45.45 5-21-303 Steel Jacket 15 HP - No Holes Cut 52.27 5-21-304 Steel Jacket 20 HP - No Holes Cut 56.82 5-21-305 Steel Jacket 30 HP - No Holes Cut...
  • Page 78 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) Burner Assembly - Parts (Common) 2-40-605 1/3 HP 115/230/60/1 Burner Motor 3450 RPM 9.55 2-40-606 1/3 HP 230/460/60/3 Burner Motor 3450 RPM 9.09 2-40-603 1/3 HP 110/220/50/1 Burner Motor 2850 RPM 11.36 2-40-770 1/3 HP 380/50/3 Burner Motor 2850 RPM...
  • Page 79 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-30-118 Air Switch 4-100 HP 0.72 0.33 5-20-019 Burner Plate Gas - 4 HP 0.45 5-20-007 Burner Plate Gas - 6 & 10 HP 0.45 5-20-055 Burner Plate Gas - 9.5 HP 0.91 5-20-013 Burner Plate Gas - 15 &...
  • Page 80 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-30-102 1/2" Gas Pressure Regulator RV 48 0.32 2-30-104 1" Gas Pressure Regulator - RV 53 0.68 2-30-105 1-1/4 " Gas Pressure Regulator - RV 61 2.27 2-30-106 1-1/4"...
  • Page 81 Gas Train Assembly - 40 - 50 HP - Propane Gas 31.82 7-54-1057 Gas Train Assembly - 60 HP - Propane Gas 31.82 Water Column 5-20-022 Fulton Water Column Bottle Casting -4-100 HP 9.09 2-30-151 MM 150 Pump Control 11.36 2-30-193 MM 150 - M/R Control 11.36...
  • Page 82 1/4"Male-Female Ball Valve for Water Column 0.27 2-40-021 Probe Basket 0.05 0.02 Panel Box Parts 2-40-420 Fulton Pump Relay-120V 0.23 2-40-421 Fulton Burner Relay - 120V 0.23 2-40-422 Base for Fulton Pump Relay 0.25 0.11 2-40-423 Base for Fulton Burner Relay 0.25 0.11 2-40-405 Fulton Pump Relay - 220v 0.23...
  • Page 83 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-45-106 Green Panel Box Indicating Light - 120V 0.05 2-45-107 White Panel Box Indicating Light -120V 0.05 2-45-108 Amber Panel Box Indicating Light - 120V 0.05 2-45-110 Red Panel Box Indicating Light -120V 0.05 2-45-112 Green Panel Box Indicating Light - 220V...
  • Page 84 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-40-161 Mini Peeper For All 7800 0.23 2-40-270 Base For All 7800 0.23 2-40-272 Display Module for 7800 Controls English (Also Available in Spanish) 0.23 2-40-247 Remote Mounting Bracket for 7800 0.65 2-40-248 Extension Cable...
  • Page 85 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-30-068 3/4"-100# Safety Valve 0.91 2-30-069 3/4"-125# Safety Valve 0.91 2-30-070 3/4"-150# Safety Valve 0.64 2-30-071 3/4"-200# Safety Valve 2.32 2-30-073 3/4"-300# Safety Valve 2.35 1.07 2-30-074 1"-15# Safety Valve 2-30-075 1"-75# Safety Valve 1.82...
  • Page 86 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 5-10-397 Tee Handle Wrench 1.23 2-20-110 Fan Puller - 5/8" Hub 0.91 2-20-115 Fan Puller - 1" Hub 0.91 Barometric Controls 2-30-092 6" MGI 4, 6 & 10 HP - Gas 1.36 2-30-095 8"...
  • Page 87 Parts Approx. Approx. Part No. Description Net Weight Net Weight (lbs.) (kgs.) 2-12-528 Scroll Gasket - 4 HP 0.45 2-12-529 Scroll Gasket - 6-15 HP 0.45 2-12-530 Scroll Gasket- 20-30 HP 0.45 2-12-531 Scroll Gasket- 40-60 HP 0.45 2-12-537 Stack Extension Gasket 6" 4-10 HP 0.45 2-12-538 Stack Extension Gasket 8"...
  • Page 88 Parts 79-G 1/01...
  • Page 89 Parts Burner Motor (1) Part No.* Part No. LP Gas Orifice (6) 2-40-605 1/3 HP 115/230/60/1 3450 4-15 Nat. Gas Orifice 2-40-606 1/3 HP 230/460/60/3 3450 4-15 7-20-050 7-20-030 2-40-603 1/3 HP 110/220/50/1 2850 4-15 7-20-051 7-20-061 2-40-770 1/3 HP 380/50/3 2850 4-15 2-20-078...
  • Page 90 Parts Gas Burner Ignition Assembly Gas Burner Components 81-G 1/01...
  • Page 91 Parts Gas Head Assemblies Part No. Complete Gas Head Assembly 7-54-1000 Natural Gas 7-54-1001 Natural Gas 7-54-1002 Natural Gas 7-54-1003 Natural Gas 7-54-1004 Natural Gas 7-54-1005 Natural Gas 7-54-1006 Natural Gas 40-50 7-54-1007 Natural Gas 7-54-1050 Propane Gas 7-54-1051 Propane Gas 7-54-1052 Propane Gas 7-54-1053...
  • Page 92 Parts Gas Head Assembly (CSD-1) 4 to 50 HP Gas Head Assembly (CSD-1) 60 HP 83-G 1/01...
  • Page 93 Panel Box Parts Part No. Motor Contactors (Three Phase) Part No. Relays 2-40-568 Contactor -AB -100- A09NA3- 220V 4-60 2-40-420 Fulton Pump Relay - 120V 4-100 2-40-567 Contactor- AB -100- A09ND3-120V 4-60 2-40-421 Fulton Burner Relay - 120V 4-100 2-40-641...
  • Page 94 Parts Water Column - Parts Part No. Water Column Bottle Casting (1) 5-20-022 Water Column Bottle Casting 4-30 5-20-048 Water Column Bottle Casting 50-100 Part No. Water Gauge Glass (2) 2-12-017 9-1/4" Water Gauge Glass - Corning 4-100 2-12-065 8-5/8" Extra Heavy Gauge Glass Part No.
  • Page 95: Warranty

    Warranty 8 -G 1/01...
  • Page 96   87-G 1/01...
  • Page 97: Standard Warranty For Fulton Boilers

    Fulton Companies has been advised of the possibility of such damages. Fulton’s liability shall never exceed the amount paid for the original equipment found to be defective.
  • Page 98   89-G 1/01...
  • Page 99 Fulton shall in no event by liable for any consequential or incidental damages arising in any way, including but not limited to any loss of profits or business, even if Fulton has been advised of the possibility of such damages.
  • Page 100   91-G 1/01...
  • Page 101: Component Data Sheets

    Component Data Sheets -G 1/01...
  • Page 102  ...

Table of Contents