Boiler Dimensions And Operating Requirements - FULTON PHW 300 Installation And Operation Manual

Gas pulse combustion hydronic heating boiler
Table of Contents

Advertisement

INSTALLATION
Model
Speci cations
Input
Nat. Gas consumption @ rated
capacity
Propane Consumption @rated
capacity
Electrical Requirements
(Amps: Max/Run)
MAWP
Water Content
Dry Weight
Operating Weight
Dimensions
A. Boiler Width
B. Overall Boiler Height
C. Overall Boiler Depth
D. Exhaust Outlet Diameter
E. Air Inlet Diameter
F. Water Inlet/ Outlet Diameter
G. Min. Clearance to Ceiling
H. Min. Clearance to Either Side Wall
I. Min. Clearance in Front of Boiler
J. Min. Clearance Behind Boiler
G
Front View
2-4
TABLE 1 BOILER DIMENSIONS AND OPERATING REQUIREMENTS
PHW
300
BTU/Hr
300,000
FT3/Hr
300
FT3/Hr
120
120V/60/1
4.2/0.6
240V/60/1
2.1/0.3
PSI
160
BAR
4.1/11.0
Gal
34
LB
1395
LB
1680
IN
27.5
IN
71.25
IN
53.25
IN
4
IN
3
IN
2
IN
24
IN
1
IN
36
IN
24
F
D
Back View
FIGURE 2 PULSE COMBUSTION HYDRONIC BOILER
500
750
500,000
750,000
500
750
200
300
4.2/0.6
4.2/0.6
2.1/0.3
2.1/0.3
160
160
4.1/11.0
4.1/11.0
34
42
1395
1800
1680
2150
27.5
27.5
71.25
83.2
53.25
51.3
4
4
3
4
2
2
24
24
1
1
36
36
24
24
E
I
B
A
SECTION 2
PHW-IOM-2013-0214
1000
1400
1,000,000
1,400,000
1000
1400
400
560
4.2/0.6
4.2/0.6
2.1/0.3
2.1/0.3
160
160
4.1/11.0
4.1/11.0
42
80
1800
2230
2150
3195
27.5
33.6
83.2
88.1
51.3
62.6
4
4
4
4
2
2.5
24
24
1
1
36
36
24
24
C
H
F
Top View
© The Fulton Companies 2013
2000
2,000,000
2000
720
10/.75
5/0.4
160
4.1/11.0
75
2900
3500
33.6
89
70.1
6
6
4 Flanged
24
1
36
24
J

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Phw 1000Phw 1400Phw 500Phw 2000Phw 750

Table of Contents