Manual Control (Manual Request For Output) - FULTON Vantage VTG Series Installation And Operation Manual

Condensing hydronic boilers standard, dual fuel, and low emissions models 2,000,000 - 6,000,000 btu/hr 504k - 1.5 mm kcal/hr
Hide thumbs Also See for Vantage VTG Series:
Table of Contents

Advertisement

OPERATION
ƒ Manual Control (Manual Request for Output)
3-10
VTG-IOM-2016-1214
1) Burner is in operation mode.
a. The display shows oP: on the left, the percentage of
the current output on the right.
2) Press and Hold the F button for 1 second.
a. The display shows LoAd:, the current output flashes.
3) Still holding the F button press the – or + to adjust the
required output in manual.
a. The display shows LoAd:, still holding the F button
the new output flashes.
4) Release the F button.
a. The current manual output flashes; oP: is still
displayed on the left solid indicating that manual
control is activated.
5) Press and hold the – and + for 3 seconds to return to
automatic mode.
a. The output will no longer flash, oP: will be displayed
on the left solid and the operating percentage will
be displayed on the right.
SECTION 3
© The Fulton Companies 2016