FIGURE 12 - OIL PUMP DETAILS (VTG-2000DF TO VTG-4000DF)
FIGURE 13 - OIL PUMP DETAILS (VTG-5000DF/VTG-6000DF)
2-24
VTG-IOM-2016-1214
Figure 12 Notes
Characteristic
1
Suction
2
Return
3
Pressure Gauge Attachment
4
Vacuum Gauge Attachment
5
Pressure Regulator
6
Outlet to Burner
Minimum Delivery Rate at 174
PSI Pressure
Delivery Pressure Range
Maximum Suction
Oil Viscosity Range
Maximum Fuel Oil
Temperature
Pressure Calibration at the
Factory
Figure 13 Notes
Characteristic
1
Suction
2
Return
3
Pressure Gauge Attachment
4
Vacuum Gauge Attachment
5
Pressure Regulator
6
Outlet to Burner
Minimum Delivery Rate at 174
PSI Pressure
Delivery Pressure Range
Maximum Suction
Oil Viscosity Range
Maximum Fuel Oil
Temperature
Pressure Calibration at the
Factory
SECTION 2
Connection/Detail
3/8" NPT (Piped in the Field)
3/8" NPT (Piped in the Field)
G 1/8" (Completed at Factory)
G 1/8" (Completed at Factory)
¼" NPT (Completed at Factory)
54 GPH (204.41 LPH)
145 – 290 PSI (997.7 - 1999.5 k Pa)
13 " Hg
2.8 – 75 cSt
140 F (60 C)
198-200 PSI (1365 - 1379 kPa)
Connection/Detail
1/2" NPT (Piped in the Field)
1/2" NPT (Piped in the Field)
G 1/4" (Completed at Factory)
G 1/4" (Completed at Factory)
1/2" NPT (Completed at Factory)
132 GPH (500 LPH)
102-435 PSI (703 - 3000 k Pa)
13 " Hg
3 – 75 cSt
302 F (150 C)
365-385 PSI (2516.6 - 2654.5 kPa)