Setpoint Configuration with Outdoor Reset

The Setpoint Configuration screen displayed is based on the option selected. Below is the Setpoint Configuration
screen with outdoor reset. The settings are the same as those without the outdoor reset with the following
changes/additions.
Setpoint Mode:
o
ModSync: The ModSync Setpoint mode will now use the outdoor reset configuration on the next
screen.
o
Manual: When in Manual mode the ModSync will operate based on the user selected input.
Outdoor Temp Disable: If the Outdoor Air Temperature exceeds the Outdoor Temp Disable value, the
ModSync will disable the boilers and not allow them to run. The boiler status will change to Outdoor
Temp Disable to show that the boiler has been disabled due to high outdoor air temperature.
Outdoor Temp Deviation: Outdoor Temp Deviation is how many degrees the outdoor air temperature
needs to drop before the ModSync will re-enable the boilers out of Outdoor Temp Disable.
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
Figure 18 – Setpoint Configuration with Outdoor Reset
31