OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
3-18
ƒ Yokogawa UT 32A Basic Programming:
` CHANGE SET POINT
1. SP (set point) display reads current set point in degrees F.
2. Press the SET/ENTER button to change the set point. Use left and right
arrows to navigate to digit you wish to change. Press up/down arrow to
change digit. When complete, press SET/ENTER again to set the new value.
` SET BOILER ON/OFF TEMPERATURE
1. There are two parameters that are required to set up the hysteresis around
the set point. These parameters are HY1 and A1.
2. To access HY1: Press the DISP button until HY1 appears. Factory default
setting is 10.
3. To navigate to A1: Press the DISP button until A1 appears. Factory default
setting is -5.
NOTEE:
The following is an example. With these default settings and a set point of
140°F, the boiler would turn on at 135°F and turn off at 145°F.
` SET PROPORTIONAL BAND, INTEGRAL AND DERIVATIVE VALUES
1. To navigate to PID press the Fn button. Use the down arrow to scroll from
(P) to (I) and to (D)
2. To make a Proportional (P) value change press SET/ENTER and use the left/
right and up/down arrows to change the digits. Press SET/ENTER to set the
new valve.
NOTEE:
The higher the Proportional (P) value, the sooner the boiler will begin to
drop to low fire near set point. The smaller this value, the longer the boiler will
remain at high fire before dropping to low fire near set point.
3. Use the up/down arrows to navigate to Integral (I). To make a value change
press SET/ENTER and use the left/right and up/down arrows to change the
digits. Press SET/ENTER to set the new value.
NOTEE:
The smaller the Integral (I) value, the more quickly the boiler will react to a
change in temperature.
4. Use arrows to navigate to Derivative (d). Default setting is "OFF". Alteration
is not recommended.
5. Pressing DISP will take return you to front screen.