Operating Controls

The following specifications, data, equipment and operating
descriptions apply to typical Vertical Boiler units. These
sections are provided for general information purposes only,
and do not necessarily reflect the specific details of individual
systems.
At commissioning, the operation of all safeties and interlocks
should be verified. Setpoints of all pressure and temperature
switches as well as the programs for all programmable
controls (pressure controls, pressure limits, operating controls,
servo motors etc.) should be recorded for future reference.
Contact the Fulton Service Department with any questions
regarding the proper operation, set points and verification
procedures for these controls.

Burner Settings

Burner combustion settings:
ƒ Boiler is fully test fired at the factory, please refer to the
test fire sheet for combustion information.
» P0 set point is typically between P1 and P2 on
combustion curve.
NOTE:
Pilot pressure range is to be 2.5" w.c. to 3.5" w.c.
» Lower O2 settings can reduce burner mesh life.
» Higher O2 settings will reduce the overall
efficiency of the burner.
ƒ Boiler pressure controller is Yokogawa UT-32A for the
VSRT 9.5-125 and a Fulton PLC Controller for the
VSRT-250.
* Please refer to the PURE Control manual for the
VSRT-250
Burner combustion adjustment guidelines:
Up
Fan Speed Adjustment
More O2, More Input
Gas Servo Adjustment
More Input, Less O2
Air Servo Adjustment
More O2, Less Input
SKP-25 Adjustment
More Input, Less O2
Questions? Please Contact Your Local Manufacturer's Representative

Pressure Modulation Controller

ADJUSTMENT OF THE YOKOGAWA UT-32A OPERATING
CONTROLLER FOR VSRT 9.5-125 BHP:
Front panel keys are shown below and explained in the text
that follows.
ƒ
ƒ
ƒ
ƒ
ƒ
Down
ƒ
Less O2, Less Input
Less Input, More O2
Parameter set-point adjustments are shown in the figure on
Less O2, More Input
the next page and explained in the text that follows.
Less Input, More O2
(1) – DISP key used to switch the Operation Displays.
Press the key in the Menu Display or Parameter
Setting Display to return to the Operation Display.
(2) – PARA key hold down the key for 3 seconds
to move to the Operation Parameter Setting
display. Hold down the key and the left arrow key
simultaneously for 3 seconds to move to the Setup
Parameter Setting Display. Press the DISP key in the
Parameter Setting Display to return to the Menu
Display. Press the SET/ENTER key once to cancel the
parameter setting (set point is blinking)
(3) SET/Enter key press the key in the Menu Display to
the Parameter Setting Display of the Menu. Press the
key in the Parameter Setting Mode to change the set
point.
(4) – Light-loader interface is the communication
interface to the adapter cable when setting and
storing parameters via PC.
(5) – A/M key used to switch between AUTO and
MAN modes.
(6) – Fn user function key defined by user. PID will
display when Fn key is pressed.
OPERATION
3-9