SECTION 3
VTG-IOM-2016-1214
ƒ Parameter Restore
Questions? Please Contact Your Local Manufacturer's Representative
1. Press and hold "F and A" until Code is displayed
a. Then enter unit national board number press enter
once complete.
2. "400: Set" will be displayed
a. Press the "-"arrow two times until "100: PArA" is
displayed.
b. Press the Enter button to get into "100" parameters.
c. Press the "+" arrow until parameter 113 is reach enter
into the parameter and record the Burner ID#.
d. This is required for performing the Restore process.
3.
Restore procedure:
a. Go to "000: Int" parameter enter in and go to P-050 (050
will be flashing).
b. Press enter > bAC_uP is displayed.
c. Press "+" button to select "rEStorE".
d. Press enter > 0 is displayed.
e. Press "+" button and 1 is flashing
f. Press enter, after about 5 seconds a 0 appears on the
display indicating the end of the backup process.
g. Note: If an error occurs during the Restore process, a
negative value is displayed. For troubleshooting go
error code 137 to view diagnostic code.
OPERATION
3-15