Operating Controls; Burner Settings; Pressure Modulation Controller - FULTON VSRT Series Installation And Operation Manual

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

Operating Controls

The following specifications, data, equipment and
operating descriptions apply to typical Vertical
Boiler units. These sections are provided for general
information purposes only, and do not necessarily
reflect the specific details of individual systems.
At commissioning, the operation of all safeties and
interlocks should be verified. Setpoints of all pressure
and temperature switches as well as the programs for
all programmable controls (pressure controls, pressure
limits, operating controls, servo motors etc.) should
be recorded for future reference. Contact the Fulton
Service Department with any questions regarding the
proper operation, set points and verification procedures
for these controls.

Burner Settings

Burner combustion settings:
ƒ Typical O2 for proper combustion is 4.5-6%.
ƒ Typical O2 for the ignition position (P0) is 3.5-5%
for reliable light off and flame sensing..
» P0 set point is typically between P1 and P2
on combustion curve.
 OTE:
Pilot pressure range is to be 2.5" w.c.
to 3.5" w.c.
» Lower O2 settings can reduce burner mesh
life.
» Higher O2 settings will reduce the overall
efficiency of the burner.
ƒ Boiler pressure controller is Yokogawa UT-32A.
Burner combustion adjustment guidelines:
Up
Fan Speed Adjustment
More O2, More Input
Gas Servo Adjustment
More Input, Less O2
Air Servo Adjustment
More O2, Less Input
SKP-25 Adjustment
More Input, Less O2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com

Pressure Modulation Controller

ADJUSTMENT OF THE YOKOGAWA UT-32A
OPERATING CONTROLLER:
Front panel keys are shown below and explained in the
text that follows.
ƒ
ƒ
ƒ
ƒ
ƒ
Down
Less O2, Less Input
ƒ
Less Input, More O2
Less O2, More Input
Parameter set-point adjustments are shown in the figure
Less Input, More O2
on the next page and explained in the text that follows.
(1) – DISP key used to switch the Operation Displays.
Press the key in the Menu Display or Parameter
Setting Display to return to the Operation Display.
(2) – PARA key hold down the key for 3 seconds
to move to the Operation Parameter Setting
display. Hold down the key and the left arrow key
simultaneously for 3 seconds to move to the Setup
Parameter Setting Display. Press the DISP key in the
Parameter Setting Display to return to the Menu
Display. Press the SET/ENTER key once to cancel the
parameter setting (set point is blinking)
(3) SET/Enter key press the key in the Menu Display
to the Parameter Setting Display of the Menu. Press
the key in the Parameter Setting Mode to change
the set point.
(4) – Light-loader interface is the communication
interface to the adapter cable when setting and
storing parameters via PC.
(5) – A/M key used to switch between AUTO and
MAN modes.
(6) – Fn user function key defined by user. PID will
display when Fn key is pressed.
OPERATION - 3
3-7
VSRT_IOM_2018-1213