Fulton Endura Boiler
Modbus Communication to a SOLA Display
Purpose:
To show the configuration of the SOLA display to accommodate communication to the ModSync SE.
The SOLA base only communicates to via a baud rate of 38400 and the ModSync only communicates
at a baud rate of 19200 to the boilers.
Procedure (Wiring):
The SOLA Display will typically be wired from MB1 on the SOLA Base to COM 1 on the SOLA Display.
***Please not that this can vary with the job and application. Verify the communication wiring before
proceeding.
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
The back center of the SOLA Display will contain the
connections for the Modbus networks COM1 and
COM2.
COM 2 will most commonly be used in these setups
for the ModSync connection.
43