SECTION 3
VTG-IOM-2013-0815
10. Observe the status of the burner by going to OperationalStat >
NormalOperation.
11. Turn the main ON/OFF switch to OFF. The control will now post purge.
12. Follow the Pre-Ignition steps again to verify ignition with the new gas
pressures.
13. Turn the main burner switch to OFF. The control will now post purge.
14. Change the operation to Automatic under ManualOperation > Auto/
Manual/Off and press Enter and confi rm Automatic is entered in the
current fi eld.
15. Press Escape four times. Select PW Logout, the password is now logged
out.
16. Press Escape twice. Select OperationalStat > NormalOperation. The control
is now on the normal operational display screen.
17. The boiler is now ready to run. Adjust your setpoint on the temperature
control to the desired temperature and turn the main ON/OFF switch to
ON for the burner to operate.

Operating Temperatures and Fuel Selection

Use Table 6 to determine minimum return water temperature requirements:
TABLE 6 - MINIMUM RETURN WATER TEMPERATURES
Fuel
Natural Gas
Propane
#2 Fuel Oil
B100 Bio-Diesel
#2 Fuel Oil with guaranteed <15
ppm Sulfur
Digester Gas/Alternative Fuels

Temperature Controller Instructions

The Siemens LMV37 and LMV51 controls may be paired with a temperature
controller. Options include the SC-500 Temperature Controller, the Yokogawa UT
32A, and the Siemens RWF40.
 SC-500 Temperature Controller Basic Programming
 CHANGE SET POINT
1. Set Point Mode is accessed through the switch selection or BMS screen
selection.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
Minimum Return Water Temperature
No minimum return water temperature
No minimum return water temperature
140°F (60°C)
100°F (38°C)
100°F (38°C)
Consult Factory
OPERATION
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
3-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents