Modsync Alarms; Backing Up The Program; Battery Replacement - FULTON Vantage VTG Series Installation And Operation Manual

Condensing hydronic boilers standard, dual fuel, and low emissions models 2,000,000 - 6,000,000 btu/hr 504k - 1.5 mm kcal/hr
Hide thumbs Also See for Vantage VTG Series:
Table of Contents

Advertisement

ModSync Alarms

Message
System Active / No Alarm
Outdoor RTD Sensor Error
Loop RTD Sensor Error
Boiler (#) Alarm
Boiler (#) Monitor Alarm
Boiler (#) Modbus Error

Backing up the Program

Used so that the program is not lost when replacing the battery or the controller is powered down. Works for
Color, SC, and LX screens only. Note: This process does not save customer settings.
1. Press and hold the screen for 5-10 seconds until the 'Info Mode' Screen is displayed. Select 'Enter Info
Mode'.
2. Enter the password of '1 1 1 1 'and then press enter.
3. Select 'Flash Memory' from the 'Information Mode Main Menu'.
4. Select 'Backup User Application' from the 'Flash Memory' menu.
5. Select 'Yes'. The Controller will now cycle and backup the program. This could take several minutes.
6. When complete the DLU with display 'This app is already backed up'. Press 'ESC' to three times to exit
Info Mode.

Battery Replacement

A 3V coin style lithium battery with part number CR2450N is installed in every ModSync screen. The battery is
responsible for the backup of the program, system data, and user settings. It is recommended that the battery be
replaced every 3-5 years to prevent issues such as loss of program or customer settings.
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
Explanation / Recommended Action
The ModSync is active and no alarms are sensed.
The Outdoor Sensor is providing a value that is outside of the allowable scale. Verify
the RTD wiring, replace the sensor if necessary.
The Hydronic Loop Sensor is providing a value that is outside of the allowable scale.
Verify the RTD wiring, replace the sensor if necessary.
The Local boiler controls have indicated that an alarm condition occurred.
The ModSync called for the boiler to start and the main gas valve inputs was not
received within a customer adjustable 5 minutes. Check the limit string of the boiler
to verify which device is preventing the boiler from enabling. Verify the operating
limits are set higher than the maximum loop temperature variable on the ModSync.
Issues with the Modbus communication between the ModSync and the specified
boiler. Check wiring and local boiler control settings. See section 4 of this manual for
local boiler control setup and addressing.