Procedure (SOLA Settings):
From the 'Home' Screen select 'Setup' in the lower right corner, then select 'Display Setup' from the
'Setup' Menu.
Determine where the wiring for the ModSync Port 2 communication is landed. On a typical setup
COM 1 will be the communication from the SOLA Display to the SOLA Base, leaving COM 2 open to
communicate to the ModSync. Select the tab and enable the port that is to be used, make sure the
Modbus address you wish you use is within the defined range and select a baud rate of 19200.