Changing An Existing Curve; Creating A New Curvepoint; Loadlimits; Shutdown - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Changing an existing curve

Menu level 1
Params & Display

Creating a new curvepoint

16. Load limits
Menu level 1
Params & Display

17. Shutdown

Menu level 1
ManualOperation
Siemens Building Technologies
HVAC Products
The curvepoints can be changed during burner off periods (Phase 12) or during burner
operation (Phase 60).
To change an existing curve, select the curvepoint in «Point» mode. You are now able
to change the point, or to cancel it.
Menu level 2
Menu level 3
RatioControl
GasSettings
To create a new curvepoint, select «Manual». Set the output of the new point and ac-
knowledge by pressing Enter .
During the manual procedure, the actuators travel on the interpolated straight lines be-
tween the curvepoints.
After pressing Enter , each individual actuating device can be selected to optimize the
position.
To leave the curvepoint setting, press the ESC button and store the point by pressing
Enter .
Finally, you can limit the burner output to a minimum and maximum in accordance with
the boiler's requirements.
Menu level 2
Menu level 3
RatioControl
GasSettings
Choose «Autom/Manual/Off» to select «BurnerOff».
Menu level 2
Menu level 3
Autom/Manual/Off
Basic Documentation LMV5...
8 Commissioning instructions for the LMV5... system
Menu level 4
Menu level 5
CurveParams
Point
Manual
Menu level 4
Menu level 5

LoadLimits

MinLoadGas
MaxLoadGas
Menu level 4
Menu level 5
Menu level 6
Menu level 6
Menu level 6
157/301
CC1P7550en
13.08.2004