Error
Diagnostic
Device
code
code
03
87
ABE
88
#
All
01
88
SA
02
88
LC
03
88
ABE
04
88
VDS module Fault Feedback VSD Module
05
88
O2M
90
---
SA
91
---
SA
92
---
SA
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Fault Feedback AZL5...
No feedback for max. number
Plausibility fault NMT
Fault Feedback Actuator
Undefined fault class of SA
Fault Feedback Load Controller
Undefined fault class of LC
Fault Feedback AZL
Undefined fault class of AZL
Undefined fault class of VSD module
Fault Feedback O2 Module
Undefined fault class of O2 module
Fault Feedback Aux Actuator 3
Basic unit has detected a ROM-CRC er-
ror on the air actuator when checking its
feedback signal
Fault Feedback Air Actuator
Basic unit has detected a ROM-CRC er-
ror on the air actuator when checking its
feedback signal
Fault Feedback Gas (Oil) Actuator Basic unit has detected a ROM-CRC er-
ror on the gas actuator when checking its
feedback signal
Meaning for the LMV5x system
Troubleshooting
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective AZL...(see diag-
nostic code) or basic unit
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
227/301