Siemens LMV51 Series Basic Documentation page 243

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A9
1B
VSD module Internal Fault VSD Module
A9
1E
VSD module Internal Fault VSD Module
A9
1F
VSD module Internal Fault VSD Module
AB
#
O2M
AB
01
O2M
AB
02
O2M
AB
04
O2M
AB
05
O2M
AB
07
O2M
AB
08
O2M
AB
09
O2M
AB
0A
O2M
AB
10
O2M
AB
12
O2M
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Fault when copying a parameter page
External plausibility fault. This type of fault
covers possible faults occurring due to in-
valid presettings in the drive commands.
In response, the presettings will be ig-
nored
Internal plausibility fault. This type of fault
detects faults that cannot practically oc-
cur...
Fault O2 Module
The O2 module has detected own fault
and reported it to the basic unit
Internal Fault O2 Module
CRC fault during ROM test
Internal Fault O2 Module
CRC fault during RAM test
Internal Fault O2 Module
Fault during key value check
Internal Fault O2 Module
Error code for time block overflow
Internal Fault O2 Module
Sync fault or CRC fault
Internal Fault O2 Module
Error code for main loop counter
Internal Fault O2 Module
Fault during stack test
Internal Fault O2 Module
Feedback values invalid
Unplaus Value Nernst Voltage
Nernst voltage outside the valid range
O2 Module
Unplaus Value Thermocouple
Thermocouple voltage outside the valid
O2 Module
range
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
Check the special positions for valid value range (0-100 %)
*1)
*2)
*2)
*2)
*2)
*2)
*2)
*2)
*2)
Check the connection (correct polarity, short-circuit)
Check connections (polarity, short-circuit, open-circuit).
Check power supply to the O2 module.
Check fuse F2 on the O2 module.
Check heating control on the QGO.
243/301
CC1P7550en
13.08.2004