Siemens LMV51 Series Basic Documentation page 267

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
19.3 Precontrol
As a result of the measurements made when setting the O
the behavior of the burner will be acquired. Based on the type of fuel, the O
O
setpoint and the standardized value, precontrol calculates the air rate in a way that
2
the O
setpoint will be reached as long as the environmental conditions do not change,
2
irrespective of burner output.
Calculation of the air rate from the manipulated variable is made such that a manipulated
variable of +10 % will offset an air density change of –10 %.
19.3.1
Calculation of precontrol
Based on the settings for O
teristics and behavior of the burner. The lambda factor, which is taken into considera-
tion when calculating the air rate reduction, reflects these values which are gained from
practical experience.
Precontrol can be calculated in 2 different ways:
Parameter:
Type Air Change (like P air, like theory)
The measured lambda factor is also considered when air density
like P air
(temperature pressure) changes. Air pressure and air density have an
impact on the fuel throughput.
The measured lambda factor is not considered when air density
like theory
(temperature pressure) changes. Air pressure and air density have no
impact on the fuel throughput.
Recommendation:
With gas: like P air
With oil: like theory
Basic Documentation LMV5...
19 Addendum 4: LMV52... with O2 trim control and O2 module
trim control, the system becomes familiar with the charac-
2
setpoint, the properties and
2
ratio, the
2
267/301
CC1P7550en
13.08.2004