Siemens LMV51 Series Basic Documentation page 212

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
19
01..2F
SA
19
01
SA
19
02
SA
19
04
SA
19
08
SA
19
20
SA
1A
1
BU
1B
#
BU
1C
#
BU
212/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Actuator
The diagnostic value is made up of the fol-
lowing faults or their combinations (the in-
dividual diagnostic codes are added up in
hexadecimal format)
Internal Fault Actuator
Fault occurred on the air actuator when
comparing potentiometer channels A and
B
Internal Fault Actuator
Fault occurred on the active fuel actuator
when comparing potentiometer channels A
and B
Internal Fault Actuator
Fault occurred on auxiliary actuator 1
when comparing potentiometer channels A
and B
Internal Fault Actuator
Fault occurred on auxiliary actuator 2
when comparing potentiometer channels A
and B
Internal Fault Actuator
Fault occurred on auxiliary actuator 3
when comparing potentiometer channels A
and B
Slope too steep
Slope of curve section is too steep
Operation in Parameter Setting
Programming mode is still active in Phase
Mode quit
62 and the target positions (normal opera-
tion) have not been reached
Ignition Pos not defined
The relevant ignition positions have not
been parameterized
Meaning for the LMV5x system
Troubleshooting
Check CAN cabling and terminators as specified
Check CAN cabling and terminators as specified
Check CAN cabling and terminators as specified
Check CAN cabling and terminators as specified
Check CAN cabling and terminators as specified
Check curve data. If there is a slope greater than
- 3.6° per 0.1 % (30 s ramp)
- 1.8° per 0.1 % (60 s ramp)
- 0.9° per 0.1 % (120 s ramp)
load change between 2 curvepoints -> change load as-
signment of the curvepoints such that above condition will
be satisfied
When parameterizing the curve, the plant should be oper-
ated in manual mode with "Burner on". This prevents the
load controller from triggering the change to shutdown. Re-
sponse of the TL can trigger the same action, however, but
the value (curvepoint) currently handled can still be stored
in standby or lockout
Set the ignition positions
CC1P7550en
13.08.2004