Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
SW Version
SW Version
RatioControl
GasSettings
130/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
SpecialPosi-
tions
HomePos
HomePosGas
HomePosAir
HomePosAux1
HomePosAux2
HomePosAux3
HomePosVSD
PrepurgePos
PrepurgePosAir Prepurge position of air damper (gas)
Prepurge-
PosAux1
Prepurge-
PosAux2
Prepurge-
PosAux3
Prepurge-
PosVSD
IgnitionPos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux
IgnitionPosAux2 Ignition position of auxiliary damper 2
IgnitionPosAux3 Ignition position of auxiliary damper 3
IgnitionPosVSD
PostpurgePos
PostpurgePos-
Gas
PostpurgePosAir Postpurge position of air damper (gas)
Description
SW version of burner control
Parameter settings for ratio control
Parameter settings for firing on gas
Setting the special actuator positions for firing on gas
Setting the home positions for firing on gas
Home position of fuel damper (gas)
Home position of air damper (gas)
Home position of auxiliary damper (gas)
Home position of auxiliary damper 2
Home position of auxiliary damper 3
Home position of VSD
Setting the prepurge positions for firing on gas
Prepurge position of auxiliary damper (gas)
Prepurge position of auxiliary damper 2
Prepurge position of auxiliary damper 3
Prepurge position of VSD
Setting the ignition positions for firing on gas
Ignition position of fuel damper (gas)
Ignition position of air damper (gas)
Ignition position of auxiliary damper (gas)
Ignition position of VSD
Setting the postpurge positions for firing on gas
Postpurge position of fuel damper (gas)
Value range
Access
Default pa-
LMV51 LMV52
rights
rameter
setting
0..65535
User
---
x
0..65535
User
---
User
x
Service
x
Service
x
Service
x
0..90°
Service
x
0..90°
Service
x
0..90°
Service
x
0..100 %
0..90°
Service
0..90°
Service
0..100 %
Service
Service
x
0..90°
Service
90°
x
0..90°
Service
90°
x
0..100 %
0..90°
Service
90°
0..90°
Service
90°
0..100 %
Service
100 %
Service
x
0..90°
Service
invalid
x
0..90°
Service
invalid
x
0..90°
Service
invalid
x
0..100 %
0..90°
Service
invalid
0..90°
Service
invalid
10..100 %
Service
invalid
Service
x
0..90°
Service
15°
x
0..90°
Service
15°
x
CC1P7550en
13.08.2004
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x