Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Configuration
126/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
ConfigGeneral
AlarmStartPrev
NormDirectStart
OilPumpCou-
pling
IgnOilPumpStart
ForcedIntermit
Continu-
ousPurge
FuelTrainGas
FuelTrainOil
FuelTrainReset
FuelTrainGas
FuelTrainOil
ContPilotGas
ContPilotOil
MainsFrequency
ConfigIn/Output
StartReleaseGas
Description
General parameters of burner control
With / without alarm in the event of start prevention and heat
demand
Normal / direct start in the event of heat demand in phase 78
Configuration for coupling the oil pump
Switch-on time of ignition and oil pump
With / without forced intermittent operation
Configuration for normal or continuous fan operation
Fuel train when firing on gas
Fuel train when firing on oil
Resetting the fuel train to invalid value
Continuous pilot gas
Continuous pilot oil
Selection of mains frequency 50 / 60 Hz
Configuring the inputs and outputs
Input start release gas active
Value range
Access
Default pa-
LMV51 LMV52
rights
rameter
setting
USER
x
Service
x
deactivated
Service
deactivated
x
activated
NormalStart
OEM
NormalStart
x
DirectStart
Magnetcoupl
OEM
Magnet-
x
Directcoupl
coupl
on in Ph38
OEM
on in Ph38
x
on in Ph22
deactivated
Service
activated
x
activated
deactivated
OEM
deactivated
x
activated
DirectIgniG
OEM
invalid
x
Pilot Gp1
Pilot Gp2
LightOilLO
OEM
invalid
x
HeavyOilHO
LO w Gasp
HO w Gasp
OEM
x
OEM
x
OEM
x
deactivated
OEM
deactivated
activated
deactivated
OEM
deactivated
activated
50 Hz
OEM
50 Hz
x
60 Hz
OEM
x
deactivated
OEM
StartRelGas
StartRelGas
CPI Gas
CPI Gas + Oil
CPI Oil
CC1P7550en
13.08.2004
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x