Siemens LMV51 Series Basic Documentation page 218

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
39
01
BU
39
02
BU
39
03
BU
3A
---
BU
3B
---
BU
40
---
BU
41
---
BU
42
#
BU
42
01..FF
BU
42
01
BU
42
02
BU
42
04
BU
42
08
BU
42
10
BU
42
20
BU
42
40
BU
42
80
BU
43
#
BU
43
01
BU
43
02
BU
43
03
BU
43
04
BU
43
05
BU
43
06
BU
43
07
BU
43
08
BU
218/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Basic Unit
Fault with timer1
Internal Fault Basic Unit
Fault with timer2
Internal Fault Basic Unit
Fault with timer3
No Burner ID defined
No burner identification defined
No Service Password defined
No service password defined
Internal Fault Basic Unit
Wrong contact position of SR relay
Internal Fault Basic Unit
Wrong contact position of ignition
Internal Fault Basic Unit
Wrong contact position of BV relay
Internal Fault Basic Unit
The diagnostic value is made up of the
following faults or their combinations (the
individual diagnostic codes are added up
in hexadecimal format)
Internal Fault Basic Unit
Contact position fault SV-oil
Internal Fault Basic Unit
Contact position fault V1-oil
Internal Fault Basic Unit
Contact position fault V2-oil
Internal Fault Basic Unit
Contact position fault V3-oil
Internal Fault Basic Unit
Contact position fault SV-gas
Internal Fault Basic Unit
Contact position fault V1-gas
Internal Fault Basic Unit
Contact position fault V2-gas
Internal Fault Basic Unit
Contact position fault V3-gas
Fault in connection with plausibility
check. For cause of fault, refer to diag-
nostic code
Internal Fault Basic Unit
No fuel selection
No Fuel Train defined
No defined fuel train parameterized or
undefined type of fuel
Internal Fault Basic Unit
Variable "Train" not defined
Internal Fault Basic Unit
Variable "Fuel" not defined
Internal Fault Basic Unit
Operating mode with LC not defined
Internal Fault Basic Unit
Prepurge time gas too short
Internal Fault Basic Unit
Prepurge time oil too short
Internal Fault Basic Unit
Safety time 1 gas too long
Meaning for the LMV5x system
Troubleshooting
Parameterize burner identification
Enter service password
*1)
Check output wiring
Check output wiring
*1)
Select fuel again with the AZL5...
CC1P7550en
13.08.2004