Siemens LMV51 Series Basic Documentation page 234

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A6
41
LC
A6
42
LC
A6
43
LC
A6
44
LC
A6
45
LC
A6
46
LC
A6
4A
LC
A6
4B
LC
A6
4C
LC
A6
4D
LC
234/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Load Controller
Invalid phase during parameterization of
the safety-related page P_TW
Internal Fault Load Controller
Invalid phase during parameterization of
the safety-related page P_STATUS
Internal Fault Load Controller
Invalid phase during parameterization of
the safety-related page P_SYSTEM
Parameter Set damaged
Page has been set to ABORT
Parameter Backup Restore
Page has been set to RESTO
Internal Fault Load Controller
Page has an invalid status
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Meaning for the LMV5x system
Troubleshooting
*1)
*1)
*1)
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL... pa-
rameters.
Otherwise, replace defective basic unit
*1)
*1)
*1)
*1)
CC1P7550en
13.08.2004