Legend to the sequence diagrams

Depending on the parameter, VP takes place:
between Ph62 and Ph70 or/and
between Ph30 and Ph32
Signal ON
Signal OFF
0 – 3 s
0 – 30 s
0 – 3 s
1)
Parameter:
With / without PM
2)
Parameter:
Short / long preignition time for oil only
Short / long oil pump – ON – time
3)
Delayed shutdown within TSA1 + TSA2
4)
Parameter:
Output as startup signal / PM relief valve
5)
Parameter:
Normal / direct startup
Normal startup → sequential phase = 10
Direct startup → sequential phase = 79
6)
Sequential phase = 24
7)
Only with valve proving during startup
8)
Parameter:
With / without alarm on prevention of startup
9)
Parameter:
With continuous purging
10)
Fan controlled as before
Running time when LOCK OUT = T_FanLockout
11)
Parameter:
With / without extraneous light test in STANDBY
12)
With valve proving during startup Startup phase 10
13)
Parameter:
Normal / continuous purging
Normal purging: Checking for off in 10, stop to
Ph-max time → 01
Continuous purging: Checking for on in 10 and
12, Stop up to Ph-max time → 01
"OilPressureMin", "akt_from_ts" → no check
14)
Parameter:
before TSA1 (LO, HO) or TSA2 (LOgp, HOgp)
"GasPressureMin", "deakt_xOGP" → PSmin can
15)
Parameter:
be deactivated for oil programs with gas pilot
"OilPumpCoupling", "direct_coupl" → SVoil has
16)
Parameter:
to be connected to output "Oil pump / magnetic
clutch". Output is active when fan is on and for
another 15 s after fan is switched off
17)
Parameter:
"Start / PSvalve", "PS_Reli_Inv"→ Output PS valve will be logically inverted
18)
Parameter:
"Alarm act / deact", "deactivated"→ The alarm output can temporarily be deactivated (for current error only)
Only with LMV52...: Continuous pilot gas / oil: Activated → Pilot valve is also activated in operation
19)
Parameter:
Only with LMV52...: Extraneous light, pilot phase, operating phase gas / oil → Separate flame supervision possible
20)
Parameter:
Only with LMV52...: DW-DK / CPI or StartReleaseGas → Parameter-dependent ON / OFF test
21)
Parameter:
CPI Gas: OFF test for gas trains only
CPI Oil: OFF test for oil trains only
CPI Gas+Oil: OFF test for gas and oil trains
Siemens Building Technologies
HVAC Products
Next phase
00, Rep = 0
01
12, Rep > 0
Parameter direct start
Checking with controller on
Deviation → 10
No Rep. decrement
10
70
Without VP70 with VP80
62
Stop, up to Ph – max. time → 01
Stop, up to Ph – max. time → 10
00, Rep = 0
01
12, Rep > 0
00, Rep = 0
01
12, Rep > 0
00, Rep = 0
01
12, Rep > 0
79
Param.
10
Input: don´t care
Output: OFF
Output: ON
(when R = ON)
Basic Documentation LMV5...
4 Burner control
Assignment of times:
t0
Postpurge lockout position
t01
MaxT_SafetyPhase
t10
MinTimeHomeRun
t21
MinT_StartupRel
t22
FanRunupTime
t30
PrepurgePt1
t34
PrepurgePt3
t36
MinOnT_OilPump
t38
PreignitionT_Gas / Oil
t42
PreignitionT_Off
t44
Interval1 Gas / Oil
t52
Interval2 Gas / Oil
t62
MaxTimeLowFire
t70
AfterburnTime
t74
PostpurgeT1 Gas / Oil (tn1)
t78
PostpurgeT3 Gas / Oil (tn3)
t80
VP_EvacTime
t81
VP_TimeAtmPress
t82
VP_FillTime
t83
VP_TimeGasPress
tmx1
MaxDampRunTime
tmx2
MaxT_StartupRel
tmx3
MaxT_CircHOil
TSA1
SafetyTime1
TSA2
SafetyTime2
tv
PrepurgeTime_Gas / Oil
Permissible positioning range
In Standby: actuator can travel within the permissible po-
sitioning range, but is always driven to the home position.
Must be in the home position before changing the phase
Position as supplied (0°)
90°
Actuator fully open (90°)
FGR
Flue Gas Recirculation
CPI
Closed Position Indicator
AD
Air damper
PS-VP
Pressure Switch-Valve Proving
FCC
Fan Contactor Contact
LF
Low-fire position
APS
Air Pressure Switch
PS
Pressure Switch
PoP
Post-Purge position
HP
Home Position
SR
Safety Relay
SLT
Safety Limit Thermostat
TL
Temperature Limiter
IGN
Ignition position
Repetition counter:
k)
Heavy oil
l)
Restricted startup behavior
n)
Restricted safety chain
59/301